RO - Bijlage 2.3 technische detailtekening zonnepark
Tekst van het document
6.707 2.000
4.788
0.020
SWITCH ROOM
11°
DNO
3.00
11.5
0.650
DNO
GL 23.85°
POWER STATION (3500 kVA)
1.596
2.384
GATE
statkraft prints on recycled paper, please recycle
SYSTEM SUMMARY
DETAIL A Frame side view 1:75@A1
1.850
statkraft prints on recycled paper, please recycle
C Statkraft
LAND OWNERSHIP AREA (GROSS), ha
9.46
FENCED PV AREA, ha
8.16
FENCED PERIMETER, m
1150
SUBSTRUCTURE TYPE
Fixed tilt south facing
TABLE CONFIGURATION
2 modules in portrait
TILT ANGLE, °
11
AZIMUTH ANGLE, °
-5.59
MAXIMUM TABLE HEIGHT, m
1.6
PITCH DISTANCE, m
6.707
ROW-TO-ROW SPACING, m
2
GROUND COVERAGE RATIO (GCR), %
62.4
PV MODULE TYPE & POWER, Wp
Monocryscaline bifacial, 700 Wp
PV MODULE SIZE, mm
2384x1303x35
PV MODULE QUANTITY
13230
MODULES PER STRING
30
NUMBER OF STRINGS
441
INVERTER TYPE
String
INVERTER POWER RATING, kVA
352
NUMBER OF INVERTERS
20
TRANSFORMER STATION RATING, kVA
-
NUMBER OF TRANSFORMER STATIONS
3
TOTAL PV MODULE (DC) CAPACITY, kWp 9261 TOTAL INVERTER (AC) CAPACITY, kVA
7040
MAXIMUM GRID EXPORT CAPACITY, kVA DC / AC RATIO
1.315
AC GRID / AC INV RATIO
-
LEGEND Site boundary Fence Ditch Min.
6.00
Access & construction road Power station
10.95
8.05
Switch room DNO
7.75
DNO station
19.00
11.25
PV module frame
19.00
Gate Green area HEDGE MAINTENANCE AREA 3m wide
Screening hedge
SITE BOUNDARY FENCE SITE LOCATION Lat., Long.: 51.5753, 5.4348 NTS@A1
Min. 13.890
NOTES 1. 2.
3.
Do not scale from this drawing. All dimensions are indicative and in m unless otherwise specified. All dimensions to be confirmed on site before any installation works are commenced. This drawing present an indication of the design foreseen for the project in terms of design principles and anticipated geometry ranges. The final design and resulting detail will be developed in accordance with the principles of this indicative design, but is predicted to incorporate reasonable variations, following the standard process of undertaking detailed physical site investigations, detailed engineering analysis and competitive procurement of final equipment.
EXISTING DITCH .000
100
PROPOSAL ONLY Main office in Oslo Lilleakerveien 6, P.O. Box 200, Lilleaker NO-0216, Oslo
Min. 11.50
statkraft prints on recycled paper, please recycle
CULVERT
0m
N
20m
40m
60m
80m
100m
T +47 24 06 70 00 F +47 24 06 70 01 info@statkraft.com www.statkraft.com
CULVERT
© Statkraft copyright in the drawings, information and data recorded in this document ("the information") is the property of Statkraft. This document and the information are solely for the use of the authorised recipient and this document may not be used, copied or reproduced in whole or part for any purpose other than that for which it was supplied
J
23/07/24
Green area and east-west gap increased
UZ
PP
I
02/07/24
Template updated, restriction changed
UZ
PP
REV
DATE
DESCRIPTION General Layout
SKBEN-MEIER-000 PVL-100
DRAWN APPR 1:800 SCALE A1 PAGE
1 of 1
statkraft prints on recycled paper, please recycle
9.47