TPStorage Solution Technical Proposal Issue
01
Date
04 January 2024
Solution design reference only and detailed solution subject to the actual engineering
HUAWEI TECHNOLOGIES CO. , LTD.
Copyright © Huawei Technologies Co. , Ltd. 2023. All rights reserved. No part of this document may be reproduced or transmitted in any form or by any means without prior written consent of Huawei Technologies Co. Ltd. ,
Trademarks and Permissions and other Huawei trademarks are trademarks of Huawei Technologies Co. Ltd. All other trademarks and trade names mentioned in this document are the property of their respective holders. ,
Notice The purchased products services and features are stipulated by the contract made between Huawei and the customer. All or part of the products services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract all statements information and recommendations in this document are provided " AS IS " without warranties guarantees or representations of any kind either express or implied. ,
,
,
,
,
,
The information in this document is subject to change without notice. Every effort has been made in the preparation of this document to ensure accuracy of the contents but all statements information and recommendations in this document do not constitute a warranty of any kind express or implied. ,
,
,
Huawei Technologies Co. Address:
Huawei Industrial Base Bantian Longgang ,
Shenzhen 518129 People's Republic of China Website:
https://www. huawei. com/
Email:
support @huawei.com
,
Ltd.
,
,
TPStorage Solution Technical Proposal Contents
Contents
Acronyms and Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iv 1 Advantages of the Solution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 2 Energy Storage Plant Solution Design Strategy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 2. 1 Design Basis
. .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . ..
2. 2 Design Principles
. . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . ..
7 7
3 Energy Storage Solution Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 3. 1 Energy Storage Subarray Design 3. 1. 1 System Architecture of Smart Energy Storage Plant 3. 2 System Monitoring&Communication Design Scheme
. . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . ..
8
. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . ..
8
.. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . ..
9
4 Device Specifications of an ESS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 4. 1 Smart String ESS
. . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . .
4. 1. 1 Smart String ESS.
. . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. .. .. .. . .. .. .. .. .. . .. .. .. .. .. .. . .. .. .. .. .. .. . .. .. .
4. 1. 2 Battery Management System (BMS) 4. 1. 3 Smart Cooling System
10
. . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . .
12
. . . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . .
16
4. 1. 4 Fire Suppression System 4. 2 Smart PCS
10
. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . .
18
.. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . .
19
4. 3 Smart Transformer Station 4. 4 Smart Array Controller
.. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . .
22
. . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . . .. . . .. . .
24
TPStorage Solution Technical Proposal
TPStorage Solution Technical Proposal Acronyms and Abbreviations
Acronyms and Abbreviations
Terms and Abbreviations
Full Spelling
BMS
Battery Management System
BMU
Battery Monitoring Unit
BCU
Battery Control Unit
CMU
Central Monitoring Unit
PCS
Power Conversion System
SOC
State of Charge
SOH
State of Health
TPStorage Solution Technical Proposal 1 Advantages of the Solution
1Advantages
of the Solution
Key Performance
Huawei Smart String Energy Storage Solution
Traditional Energy Storage Solution
Discharge capacity
An optimizer is configured for each battery pack to prevent capacity loss caused by mismatch of packs connected in series in a battery rack. A smart controller is configured for each battery rack to prevent capacity loss caused by cross current. As a result the lifetime discharge throughput is increased.
There is no battery pack balancing design and no optimization between battery packs in a rack. The battery racks cannot be fully charged or discharged due to mismatch between battery packs. The capacity of the battery racks cannot be fully utilized. The battery racks are directly connected in parallel without rack-level voltage adjustment. The voltage difference between racks reduces the available capacity and power.
The high-density factory pre-installation solution reduces the onsite delivery cost. Old and new batteries can be mixed allowing phased battery installation.
The initial investment and total investment are high. New batteries cannot be mixed with old batteries. As a result 30% more batteries must be installed during the initial deployment to meet future capacity needs.
Smart distributed temperature control design prolonging battery life.
Only one or two air conditioners are deployed in a container. The temperature difference can reach 10° C which shortens the battery module lifespan.
,
Investment
,
,
Smart cooling
,
,
Simplified O&M
During battery replacement the SOC does not need to be manually adjusted and periodic SOC calibration is not required. Onsite O&M personnel can directly replace battery packs reducing O&M costs by more than 90%. ,
,
Experts need to manually adjust the SOC of replacement batteries and periodically calibrate the SOC.
,
AI-powered internal short circuit detection
Internal short circuit prediction accurately detects and protects against unexpected internal short circuits to improve the safety of the energy
Internal short circuits cannot be identified which may cause a fire. ,
TPStorage Solution Technical Proposal 1 Advantages of the Solution
Key Performance
Huawei Smart String Energy Storage Solution
Traditional Energy Storage Solution
storage system (ESS). Modular system design
The cooling system battery system and PCS adopt a modular design. This improves the system availability
No modular design is used. A faulty PCS affects the entire container. The system availability is only 97% to 98%.
Simplified commissioning
The operating system database and management system software are preinstalled on the server. This eliminates software and hardware compatibility risks and reduces onsite commissioning time by more than 90%.
Software is installed separately from hardware.
Security and trustworthiness
Huawei's operating system and database with proprietary intellectual property rights meet the IEC 62443 Maturity Level 3 (ML3) certification requirements.
Third-party OS and database without cyber security certification are used.
Automatic identification of cable connection topologies
The AC and DC cable connection topologies are automatically generated without manual configuration. The cable connection status and error messages are intuitively displayed. No physical check is required reducing the impact of incorrect cable connections. The device fault offline and standby status are clearly displayed.
Not supported. The wiring diagram needs to be manually configured.
Battery rack-level and battery pack-level data is displayed in 3D graphics. The SOC and charge/discharge power of all battery packs in a rack and the SOH/SOC temperature and voltage of electrochemical cells are monitored.
Information about battery packs in a rack is not displayed intuitively. Only the highest and lowest SOCs are displayed and the SOCs of other battery packs are unknown. The management granularity is coarse. Faulty packs cannot be quickly located.
,
,
,
,
,
,
3D visualization and refined management
,
,
,
,
TPStorage Solution Technical Proposal 2 Energy Storage Plant Solution Design Strategy
2Energy
Storage Plant Solution Design Strategy
2. 1 Design Basis This technical proposal mainly references the following standards: IEC 62477-1:2012 Safety requirements for power electronic converter systems and equipment - Part 1: General IEC 61000-6-2:2016 Electromagnetic compatibility (EMC) - Part 6-2: Generic standards - Immunity standard for industrial environments IEC/EN 61000-6-4: Emission standard for industrial environments EN 55011 Industrial scientific and medical equipment characteristics - Limits and methods of measurement ,
- Radio-frequency
disturbance
UL 9540A ISO 9227:2017 Corrosion tests in artificial atmospheres
—
Salt spray tests
IEC 60068-2-11:2021 Environmental testing - Part 2-11: Tests - Test Ka: Salt mist IEC 62933-5-1:2017 Electrical energy storage (EES) systems - Part 5-1: Safety considerations for grid-integrated EES systems - General specification IEC 62933-5-2:2020 Electrical energy storage (EES) systems - Part 5-2: Safety requirements for grid-integrated EES systems - Electrochemical-based systems IEC 61508-1:2010 Functional safety of electrical/electronic/programmable electronic safety-related systems - Part 1: General requirements IEC 62116:2014 Utility-interconnected photovoltaic inverters - Test procedure of islanding prevention measures IEC 61727:2004 Photovoltaic (PV) systems
- Characteristics
of the utility interface
IEC 60068-1:2013 Environmental testing - Part 1: General and guidance
2. 2 Design Principles Safety and optimal Levelized Cost of Storage (LCOS) are prioritized in the development and design of the products and features in Huawei Smart String Energy Storage Solution.
TPStorage Solution Technical Proposal 3 Energy Storage Solution Design
3Energy
Storage Solution Design
3. 1 Energy Storage Subarray Design 3. 1. 1 System Architecture of Smart Energy Storage Plant The smart energy storage plant system consists of the Smart String ESS DC LV Panel Smart Power Conversion System (PCS) Smart Array Controller (SACU) and step-up transformer. Figure 3-1 shows the architecture of the smart energy storage plant system. ,
,
,
,
Figure 3-1 System architecture of an energy storage plant
The two-level architecture of Huawei smart string energy storage solution allows flexible sub-array deployment based on AC power and DC power backup duration requirements.
TPStorage Solution Technical Proposal 3 Energy Storage Solution Design
3. 2 System Monitoring&Communication Design Scheme Figure 3-2 Monitoring network architecture of an energy storage plant
TPStorage Solution Technical Proposal 4 Device Specifications of an ESS
4Device
Specifications of an ESS
4. 1 Smart String ESS 4. 1. 1 LUNA2000-2. 0MWH-1/2H1 Huawei Smart String ESS adopts a modular design and consists of the battery cabin Smart Rack Controller Cabin and control unit cabin. It integrates the lithium iron phosphate batteries and battery racks a battery management system (BMS) heating ventilation and air conditioning system (HVAC) lighting system fire detection and automatic fire extinguishing system security system and emergency system surge protection devices (SPDs) grounding protection devices and grounding fault detection devices.
,
,
,
,
,
,
,
,
,
,
,
,
Huawei Smart String ESS 280 Ah cells (1P18S pack 57. 6 V/280 Ah 16. 128 kWh). Each battery rack contains 21 battery packs connected in series. The battery rack specifications are 1209. 6 V/280 Ah/338. 699 kWh. A 20-feet container houses six battery racks. The nominal capacity of a container is 2. 032 MWh. Each battery rack is connected to a Smart Rack Controller for independent management. The rated voltage at the high-voltage DC side of the ESS is 1250 V. ,
,
Currently Huawei provides two types of Smart String ESSs: LUNA2000-2. 0MWH1H1 (one-hour power backup as shown in Figure 4-1) and LUNA2000-2. 0MWH-2H1 (two-hour power backup). Both are standard 20-foot containers. ,
,
Figure 4-1 Appearance of LUNA2000-2. 0MWH-1/2H1
TPStorage Solution Technical Proposal 4 Device Specifications of an ESS
Table 4-1 Huawei Smart String ESS specifications Technical Specifications
LUNA2000-2. 0MWH-1H1
LUNA2000-2. 0MWH-2H1
Rated voltage at the DCDC bus side
1250 V
1250 V
Maximum voltage at the DCDC bus side
1500 V
1500 V
DCDC quantities
One DCDC for one battery rack
One DCDC for two battery racks
Rated voltage of a single rack (V)
1209. 6 V
1209. 6 V
Voltage range of a single rack (V)
1021–1380 V
1021–1380 V
Battery pack model
ESM57280AS1
ESM57280AS1
Battery pack quantities per rack
21 battery packs connected in series
21 battery packs connected in series
Nominal capacity of a single rack (kWh)
338. 7 kWh (280 Ah cells)
338. 7 kWh (280 Ah cells)
Nominal power (kW)
6 x 338 kW (280 Ah cells)
3 x 338 kW (280 Ah cells)
Rated charge and discharge current (A)
6 x 275. 2 A
3 x 275. 2 A
Charge and discharge rate
≤ 1C @40℃
≤ .5C @40℃
Intra-rack equalization mode
Pack-level proactive equalization
Pack-level proactive equalization
Rack quantities per container
6
6
Battery capacity per container (kWh)
2032 kWh
2032 kWh
Container dimensions (H x W x D)
20 ft: 2896 mm x 6058 mm x 2438 mm
20 ft: 2896 mm x 6058 mm x 2438 mm
Weight
≤ 30T
≤ 30T
IP rating
IP55
IP55
Operating temperature
–30°C to +55°C
–30°C to +55°C
–40°C to +60°C
–40°C to +60°C
0–100% (non-condensing)
0–100% (non-condensing)
range
Storage temperature range
Operating humidity range
TPStorage Solution Technical Proposal 4 Device Specifications of an ESS
Technical Specifications
LUNA2000-2. 0MWH-1H1
LUNA2000-2. 0MWH-2H1
DC surge protection
Type II
Type II
Maximum operating altitude
4000 m
4000 m
Battery cooling mode
Industrial air conditioning
Industrial air conditioning
Auxiliary power supply
380/220 V AC
380/220 V AC
Fire suppression system
FM-200/ Novec TM 1230
FM-200/ Novec TM 1230
System communications port
Ethernet/Optical port (standard configuration)
Ethernet/Optical port (standard configuration)
System communications protocol
Modbus TCP
Modbus TCP
Environmental protection requirements
RoHS 6
RoHS 6
Standards compliance
IEC62477-1 IEC62040-1 IEC61000-6-2 EN55011 UL9540A UN38.3 etc ,
,
,
, ,
,
IEC62477-1 IEC62040-1 IEC61000-6-2 EN55011 UL9540A UN38.3 etc ,
,
,
, ,
,
Lithium batteries are important components of a Smart String ESS and the self-discharge of lithium batteries is inevitable. The time from the manufacture date to the power-on of the Smart String ESS must be shorter than eight months. Otherwise maintenance charge must be performed. If maintenance charge is not performed as required the performance and service life of lithium batteries in the Smart String ESS may be adversely affected. To obtain the manufacture date of the Smart String ESS you can check for the SN of the ESS in the delivery records or consult the service engineers of the company. ,
,
,
,
4. 1. 2 Battery Management System (BMS) The BMS is the core component of the ESS. Huawei smart BMS system adopts a four-level architecture as shown in Figure 4-2. It consists of the pack-level BMU battery rack-level BCU system-level CMU and array-level SACU to monitor protect and manage the battery system smartly. ,
,
,
,
,
,
TPStorage Solution Technical Proposal 4 Device Specifications of an ESS
Figure 4-2 Huawei BMS architecture
BMU: Battery monitoring unit that monitors and collects battery running information manages passive electrochemical cell balancing diagnoses faults and bypasses a battery pack by using the battery pack optimizer. ,
,
,
BCU: Battery control unit which collects information about all battery packs as well as the voltage and current of the entire rack through the BMU and generates alarms and protects the battery rack during charge and discharge. In addition it also delivers commands to the BMU to balance the SOC between battery packs in a rack and bypass each battery pack independently implementing pack-level optimization. ,
,
,
,
CMU: Central Monitoring Unit which manages the BMU and BCU analyzes and calculates the uploaded data processes alarms records and stores data balances loads among racks and manages the state of charge (SOC) and state of health (SOH). It also collects information about the environment monitoring system (such as the fire suppression system cooling system temperature and humidity sensor and water sensor) of the Smart String ESS to create appropriate cooling policies improve ,
,
,
,
,
,
,
,
,
,
TPStorage Solution Technical Proposal 4 Device Specifications of an ESS
battery temperature consistency and warn about and respond to fire to protect the safety of the ESS. ,
The BMS is also integrated with a direct PCS. Once the BMS detects a critical alarm such as overcurrent or short circuit it directly sends a dry contact control signal to emergency stop the DCDC and protect the system from deteriorating or affecting other devices. ,
To improve system reliability and performance Huawei BMS uses a Smart Array Controller (SACU) to coordinate and control the battery systems of the entire array. The CMU and PCS are connected to the SACU to coordinate the time sequence and logic for the three levels of battery system protection and PCS protection. The hierarchical protection actions are designed based on the time sequence delay and probability of partial fault protection failure of protection units. The SACU connects to the EMS through the northbound interface to receive power grid scheduling commands and deliver them to the PCS and CMU. ,
,
,
The BMS provides the following functions: 1.
The BMS collects parameters such as the cell temperature cell voltage battery pack voltage and battery rack voltage and current in real time with hig h precision to control and optimize the operation of batteries battery packs and bat tery racks ensuring long-term efficient operation of batteries. The BMS can estimate and calibrate the SOC and SOH of batteries. It calculates displays and reports the number of cycles DOD SOC and SOH i n real time. It controls the charge and discharge of batteries based on the SOC control plan diagnoses battery faults and troubleshoots them based on fault conditions. Table 4-2 lists the supported protection levels. ,
,
,
,
,
,
2.
,
3.
,
,
,
,
,
Table 4-2 Functions of BMS components Level
Configura tion
Function
Level 1
BMU x 1/battery pack
Monitors battery cell voltage and temperature and aggregates and reports the collected data. Balances the battery voltage and SOC and bypasses battery cells as instructed by the upper-level unit. Controls the heat dissipation fan based on the temperature. Performs real-time self-test on the sampling circuit and equalization circuit and reports the self-test result in real time. Communicates with the upper-level BCU through the CAN bus. ,
,
Level 2
BCU x 1/battery rack
Monitors the total voltage and current of a battery rack and collects the temperature voltage battery current and SOC information reported by battery packs in the battery rack. Calculates the SOH of the battery rack based on the calibration operations. Manages the running and alarm information of batteries in ,
,
,
,
,
TPStorage Solution Technical Proposal 4 Device Specifications of an ESS
Level
Configura tion
Function the battery rack and controls the charge and discharge currents of the battery rack based on control requirements. Delivers equalization commands based on the voltage state of batteries in the rack. ,
Delivers insulation detection commands to the BMU based on the commands from the host. Uploads battery rack parameters and switch status to the CMU through the FE port and receives control commands from the CMU. ,
Level 3
CMU x 1 + SACU x 1
1. The CMU collects and manages level-2 BCU i nformation centrally manages the voltage current temperature SOC and bus insulation detection of t he lower level and uploads the information to the SACU through optical fibers. 2. The SACU connects to the CMU PCS management system and third-party environment monitoring system through the southbound interfaces and connects to t he E MS and SCADA through the northbound interfaces t o m anage the energy flow of the ESS. 3. The SACU calculates and collects parameters such a s the voltage current and SOC of each rack reported by the BCU and determines whether to enable the interrack balancing function of the BCU. ,
,
,
,
,
,
,
,
,
,
,
,
4. The CMU collects statistics on the overall alarm status and protection status and determines whether to turn of f the main circuit breaker for protection. 5. The CMU calculates the SOC of the connected bat teries and the battery capacity based on the cycl e count. 6. The CMU transmits data to the local management app and de livers local control commands.
4.
T he BMS collects the temperature of each battery in real time and adjusts t he heat dissipation policy of the distributed air conditioners in real time to prevent battery over-temperature. Huawei smart string energy storage solution adopts the distributed heat dissipation design. Each battery rack is independently cooled by a door-mounted air conditioner. Each battery pack is equipped with an adj ustable fan to improve the battery operating temperature consistency and reduce the temperature difference between battery packs in the container to less than 3°C (at 0. 5C). In addition the heat management function strictly monitors the operating temperature of the battery pack. If the temperature is higher or lower than the protection value a heat management start signal is generated to adj ust the temperature by adjusting the fan speed and air conditioner power. If the temperature reaches the preset hazard threshold the BMS automatically triggers the system protection mechanism to disconnect the battery loop t o ens ure system safety. ,
,
,
TPStorage Solution Technical Proposal 4 Device Specifications of an ESS
5.
Both the BMS and the PCS connect to the SACU to exchange information. The B MS supports the Ethernet optical fiber and RS485 communication ports for northbound data exchange. The BMS provides three-level balance management to balance electrochemical cells battery packs and battery racks to prevent capacity loss and cross current risks caused by inconsistency. The operating parameters of the BMS can be set on the local management app or touchscreen or remotely modified on the BMS platform (passwor d authentication supported). The operating status such as the system status analog parameter information alarm information and protection information can be di splayed on the local management app or touchscreen after passwor d authentication. The BMS can store events and historical data of the battery energy storage s ystem. It meets the IEC62619 EN ISO13849 IEC 61508 requirements and c an s tore at least 5000 events which is adequate for storing events in 30 days. Th e following figure shows the progress of the BMS IEC62619 EN ISO13849 IEC 61508 certifications issued by a third-party testing organization. ,
6.
,
7.
,
,
,
,
,
8.
,
,
,
,
,
,
,
,
4. 1. 3 Smart Cooling System The Smart String ESS adopts constant temperature and humidity design. The built-in industrial air conditioner cooling and heating system adopts the distributed temperature control design. Door-mounted air conditioners not traditional centralized air conditioners are used to maintain consistent temperature in the container. ,
,
Cool air is blown from the top and recirculated in the container to prevent dust from coming into the container. The cool air blown from the air conditioner flows along the top board to the back of the battery racks on two sides and then sucked in by the fans in battery packs. The hot air goes to the intake of the air conditioner over the top of the door. This keeps the temperature in the container at 23±5°C to ensure best operating conditions for the batteries. The air outlet temperature is low. To prevent condensation PEF thermal insulation foam is attached on the top of the container. ,
In addition through professional thermal simulation Huawei comprehensively analyzes and optimizes the thermal design based on the test results in different high and low temperature scenarios to ensure that the heat dissipation design meets the requirements. ,
,
Figure 4-3 shows the thermal simulation and air flow diagram in the 0. 5C scenario. The highest temperature in the container is 24.86°C the lowest temperature is 22.31°C and the temperature difference is only 2. 5°C. ,
,
TPStorage Solution Technical Proposal 4 Device Specifications of an ESS
Figure 4-3 Internal thermal simulation diagram of Huawei Smart String ESS
Figure 4-4 Internal air flow diagram of Huawei Smart String ESS
I n addition the temperature sensor collects temperature signals and sends them to the CMU. The CMU calculates related parameters to adjust the operating status of the air conditioner. ,
TPStorage Solution Technical Proposal 4 Device Specifications of an ESS
4. 1. 4 Fire Suppression System Huawei Smart String ESS integrates a centralized fire suppression system which consists of a gas extinguishing agent cylinder pipes nozzles signal feedback components fire detectors and extinguishant control panel emergency start/abort button horn strobe and gas release indicator. Table 4-3 describes the components of the centralized fire suppression system. ,
,
,
,
,
,
,
,
Table 4-3 Fire suppression system configuration of Huawei Smart String ESS Item Novec1230 Gas Agent Cylinder Piping Nozzle
,
,
Quantity
Remarks
1
33-34kg 9. 7% design concentration reserved residual 1 kg 38L&40L cylinders 3 nozzles
,
,
,
,
,
Fire Suppression Control Panel
1
Outside the power cabin door
Smoke detector
2
In the battery cabin of the container
Heat detector
2
In the battery cabin of the container
Horn strobe
1
Outer side of the container
Fire alarm bell
1
Outer side of the container
Extinguishant release button
1
Outer side of the container
Extinguishant abort button
1
Outer side of the container
Extinguishant release indicator
1
Outside of the container
Solenoid valve
1
Works with the fire suppression cylinder
Combustible gas exhaust system
1
In the battery cabin
T he CMU monitors the combustible gas concentration cell temperature and cell voltage drop. If the CMU detects the battery thermal runaway the alarm will be reported. If both the smoke sensor and the temperature sensor detect the fire signal or the cell thermal runaway signal is detected or the emergency start button is pressed the fire extinguishing action will be triggered. After the fire extinguishing actions are complete observe for 24 hours and ensure that the ambient temperature and combustible gas concentration in the battery cabin are lower than the safety thresholds. ,
,
,
,
,
Figure 4-5 Interworking between the fire suppression system and the ESS
,
TPStorage Solution Technical Proposal 4 Device Specifications of an ESS
4. 2 Smart PCS The Smart PCS is one of the core components that converts AC to DC and vice versa. Huawei string PCS adopts a modular design and is installed outdoors. The cabinet surface is spray-painted with RAL9003 and RAL7035 with the same color. The enclosure is made of 5052 aluminum alloy and is IP66 and C5M rated with a designed service life of 25 years. It does not need to be installed in a container. This simplifies onsite installation and O&M. ,
The model of Huawei string PCS is LUNA2000-200KTL-H1 and the capacity of each device is 200 kW. Figure 4-6 shows a Huawei string PCS. ,
Figure 4-6 Picture of Huawei string PCS
TPStorage Solution Technical Proposal 4 Device Specifications of an ESS
Table 4-4 lists the specifications of Huawei LUNA2000-200KTL-H1 200 kW PCS. Table 4-4 Technical specifications of Huawei LUNA2000-200KTL-H1 Category
Technical Specifications
LUNA2000-200KTL-H1
Efficiency
Maximum efficiency
99. 01%
DC side
Number of DC inputs
1
Maximum DC voltage
1500 V
Maximum DC power
245 kW
Maximum DC current
207. 6 A
Minimum startup voltage
540 V
Full-load voltage range
1180–1350 V (rectification mode) 1180–1280 V (inverter mode)
Operating DC voltage
1180 V to 1500 V
range
On-Grid Parameters
Off-Grid Parameters
Rated DC voltage
1180 V
Rated AC voltage
800 V
Rated AC power
200 kW
Maximum apparent power
240 kVA
Maximum active power
240 kW
Rated AC current
144. 3 A
Maximum AC current
173. 2 A
Rated AC frequency
50 Hz/60 Hz
Power factor
1 leading and 1 lagging
Maximum total harmonic distortion (rated power)
< 3%
Rated AC voltage
800 V
DC components in output voltage
± 0. 1% (with a transformer)
Output frequency
50 Hz/60 Hz
Phase difference (threephase voltage)
120±1⁰ (balanced load)
Rated output power
200 kW
Voltage THD (linear load)
< 1. 5% (0. 8 leading and 0. 8
lagging)
TPStorage Solution Technical Proposal 4 Device Specifications of an ESS
Category
Protection
Display and communication
General specifications
Technical Specifications
LUNA2000-200KTL-H1
Unbalanced load
100% unbalanced (with a transformer)
Anti-islanding protection
Supported
AC overcurrent protection
Supported
DC reverse polarity protection
Supported
DC surge protection
Type II
AC surge protection
Type II
Insulation resistance detection
Supported
Residual current monitoring unit (RCMU)
Supported
Overvoltage category
DC II/AC III
Display
LED indicators and WLAN module+app
Ethernet
Supported
USB
Supported
Dimensions (H x W x D)
875 mm × 820 mm × 365 mm
Net weight
< 99 kg
Operating temperature
–25°C to +60°C (derated at +40°C or higher)
Cooling mode
Smart air cooling
Maximum operating altitude
4000 m (derated when the altitude is greater than 2000 m)
Relative humidity
0%–100% RH
Input and output terminals
OT/DT terminal
Ingress protection rating
IP66
Topology
Transformerless
T he following figure shows the electrical diagram of Huawei LUNA2000-200KTL-H1 PCS.
TPStorage Solution Technical Proposal 4 Device Specifications of an ESS
Figure 4-7 Electrical diagram of Huawei LUNA2000-200KTL-H1
4. 3 Smart Transformer Station Huawei provides three types of typical energy storage subarrays with the power of 9 MW 6 MW or 3 MW. A 9 MW subarray is connected to the medium-voltage (MV) power grid through the 9. 0 MVA JUPITER-9000K-H0 Smart Transformer Station (STS); a 6 MW is connected to the medium-voltage power grid through the 6. 8 MVA STS-6000K-H1 STS; and a 3 MW subarray is connected to the medium-voltage power grid through the 3. 4 MVA STS-3000KTL-H1 STS. ,
Figure 4-8 Picture of STS-6000KTL-H1
T able 4-5 STS technical specifications STS model
JUPITER9000K-H0
STS6000KTL-H1
STS3000KTL-H1
Input Available PCS
LUNA2000-200KTL
Maximum LV AC Inputs
44
34
17
AC capacity
9000 kVA @ 40°C
6800 kVA @ 40°C
3400 kVA @ 40°C
Rated input voltage
800 V AC
TPStorage Solution Technical Proposal 4 Device Specifications of an ESS
STS model
JUPITER9000K-H0
STS6000KTL-H1
STS3000KTL-H1
Maximum input current at nominal voltage
2 x 3247. 7 A
2 x 2637. 8 A
2637. 8 A
Output Rated output voltage
10 / 11 / 15 / 20 / 22 / 30 / 33 / 34. 5 / 35 kV
Frequency
50 Hz
Transformer type
Oil-immersed Conservator Type
Transformer cooling type
ONAN
Tappings
±2 x 2. 5%
Transformer oil type
Mineral oil (PCB-free)
Transformer vector group
Dy11-y11
Transformer Minimum PEI Efficiency
Designed according to EN 50588-1
Transformer impedance (HV-LV1 or HV- LV2)
19% (0 ~ +10%) Semicrossing
M-voltage ring main unit
SF 6 gas insulated ring main unit
Auxiliary transformer
5 kVA li0 800 V/230 V
2. 0 kVA UPS
Optional
MV Surge Arrester for MV VCB
Optional
,
,
Dy11-y11
,
14. 6% (0 ~ +10%) Semicrossing
Dy11
7. 3% (0 ~ +10%)
5 kVA Dyn11 ,
Protection Transformer monitoring and protection
Oil level oil temperature oil pressure and buchholz
Protection Degree of MV & LV Room
IP54
Internal Arcing Fault of STS
IAC A 20 kA 1S
MV relay protection
50/51 50 N/51 N
LV overvoltage protection
Type I+II
,
,
,
General specifications Dimensions (H x W x D)
6058 mm x 2438 mm x 2896 mm
Weight
< 28 t
Operating temperature range
–25°C to +60°C
Maximum operating altitude
2000 m
< 22 t
1000 m
< 15 t
TPStorage Solution Technical Proposal 4 Device Specifications of an ESS
STS model
JUPITER9000K-H0
STS6000KTL-H1
STS3000KTL-H1
LV & MV Room Cooling
Hermetically-Sealed Smart Cooling for Higher Availability
Communications
Modbus TCP
Standards compliance
IEC 60076 IEC 62271-200 IEC 62271-202 EN 50588-1 IEC 61439-1
Modbus RTU
,
,
,
,
4. 4 Smart Array Controller The Smart Array Controller (SACU2000D) is the communication part in an energy storage subarray. It collects data from devices (including the PCSs Smart String ESSs and STSs) and reports the data to the plant monitoring backend over a fiber ring network LTE network or another type of network. ,
,
,
,
,
The SACU can be equipped with the SmartLogger PLC communications module fiber ring network switch access terminal box (ATB) PoE source communication management unit and appropriate wiring terminals and power distribution switches. ,
,
,
,
,
,
The SACU can be installed on a support pole or wall. Cables are routed in and out from the bottom. The front door can be opened for installation cable connection and maintenance. ,
,
,
,
Table 4-6 Specifications of the SACU Technical Specifications
SmartACU 2000D-D06
SmartACU 2000D-D00
SmartACU 2000D-D01
SmartACU 2000D-D03
Configurations Smart Logger
SmartLogger3000B x 1
SmartModule1000A
Optional
Ethernet
14
RS485
COM x 6 1200 / 2400 / 4800 / 9600 / 19200 / 115200 bps
Standard with 1 1 or 3 (with a SmartModule1000A) or 6 (with a SmartModule1000A and a five-port switch) ,
,
,
,
,
,
Optical Ethernet
SFP x 10 100 / 1000 Mbps ,
,
SFP x 2 100 / 1000 Mbps ,
,
,
TPStorage Solution Technical Proposal 4 Device Specifications of an ESS
Technical Specifications
SmartACU 2000D-D06
SmartACU 2000D-D00
SmartACU 2000D-D01
SmartACU 2000D-D03
Number of MBUS Module ¹
0
1
1
2
Number of SmartPID2000 Module
0
0
1
2
Environment Operating Temperature Range
-40°C ~ 60°C
Relative Humidity
4% ~ 100%(Non-condensing)
Max. Operating Altitude
4000 m ,
Electrical AC Input Voltage for Cabinet
100 V~240 V L / N (L)+ PE
AC Input Voltage for MBUS
380 V ~ 800 V 3Ph
AC Input Voltage for PID
380 V ~ 800 V 3Ph + FE (Functional Earth)
AC Input Frequency
50 Hz / 60 Hz
Power Supply
Standard: 12 V DC Optional: 24 V DC2
,
,
,
,
Mechanical Cable Entries
Bottom in & out
Maintenance
Front
Dimensions (W x H x D)
640 x 770 x 315 mm
880 x 770 x 369 mm
Weight
32 kg
49 kg
Protection Degree
IP 65
Installation Options
Wall Mounting Rack Mounting Pole Mounting
29 kg
,
,
61 kg
TPStorage Solution Technical Proposal 4 Device Specifications of an ESS
Figure 4-10 shows the appearance and dimensions of an SACU2000D. Figure 4-9 SACU picture