SG350HX Multi-MPPT String Inverter for 1500 Vdc System

HIGH YIELD

LOW COST

Up to 16 MPPTs with max. efficiency 99% 20A per string, compatible with 500Wp+ module Data exchange with tracker system, improving yield

Q at night function, save investment Power line communication (PLC) Smart IV Curve diagnosis*,active O&M

GRID SUPPORT

PROVEN SAFETY

SCR≥1.15 stable operation in extremely weak grid Reactive power response time <30ms Compliant with global grid code

2 strings per MPPT, no fear of string reverse connection 24h real-time AC and DC insulation monitoring

CIRCUIT DIAGRAM

EFFICIENCY CURVE 100% MPPT (1) AC Filter

DC EMI

AC Relay

L2 L3

MPPT (12)

DC12

Current Monitoring

DC switch

DC SPD

DC Bus

Inverter circuit

98%

L1

AC EMI

AC SPD

PE

Efficiency

DC1

96% 94%

Vdc=860V Vdc=1168V Vdc=1300V

92% 90% 88%

5%

10%

20%

30%

50%

Normalized Output Power © 2023 Sungrow Power Supply Co., Ltd. All rights reserved. Subject to change without notice. Version 20

75%

100%

Type designation

SG350HX

Input (DC) Max. PV input voltage

1500 V

Min. PV input voltage / Startup input voltage

500 V / 550 V

Nominal PV input voltage

1080 V

MPP voltage range

500 V – 1500 V

No. of independent MPP inputs

12 (Optional: 14 / 16)

Max. number of input connector per MPPT

2

Max. PV input current

12 * 40 A (Optional: 14 * 30 A / 16 * 30 A)

Max. DC short-circuit current per MPPT

60 A

Output (AC) AC output power

352 kVA @ 30℃ / 320 kVA @ 40 ℃ / 295 kVA @ 50℃

Max. AC output current

254 A

Nominal AC voltage

3 / PE, 800 V

AC voltage range

640 – 920 V

Nominal grid frequency / Grid f requency range THD

< 3 % (at nominal power)

DC current injection

< 0.5 % In

Power factor at nominal power / Adjustable power factor Feed-in phases / Connection phases

50 Hz / 45 – 55 Hz, 60 Hz / 55 – 65 Hz

> 0.99 / 0.8 leading – 0.8 lagging 3/3

Efficiency Max. efficiency / European efficiency

99.02 % / 98.8 %

Protection DC reverse connection protection

Yes

AC short circuit protection

Yes

Leakage current protection

Yes

Grid monitoring

Yes

Ground fault monitoring DC switch / AC switch PV string current monitoring Q at night function Anti-PID and PID recovery function Surge protection

Yes Yes / No Yes Yes Optional DC Type II / AC Type II

General Data Dimensions (W*H*D) Weight * Isolation method

1136 * 870 * 361 mm ≤ 116 kg Transformerless

Degree of protection

IP66

Power consumption at night

<6W

Operating ambient temperature range Allowable relative humidity range Cooling method Max. operating altitude Display Communication DC connection type AC connection type

-30 to 60℃ 0 – 100 % Smart forced air cooling 4000 m (> 3000 m derating) LED, Bluetooth+APP RS485 / PLC MC4-Evo2 (Max. 6 mm², optional 10mm²) Support OT/DT terminal (Max. 400 mm²) IEC 62109, IEC 61727, IEC 62116, IEC 60068, IEC 61683, VDE-AR-N 4110:2018,

Compliance

VDE-AR-N 4120:2018, EN 50549-1/2, UNE 206007-1:2013, P.O.12.3, UTE C15712-1:2013

Grid Support

Q at night function, LVRT, HVRT, active & reactive power control and power ramp rate control, Q-U control, P-f control