06c.3 Vergunningstekening Nieuw Erf 1 nw bestand
Tekst van het document
113
T 740
T
743
112
T
1245
T 742
T 1313
114
Venloseweg
INV
INV
INV
INV
4
N
3
1-3
2
1-3
1
S
1-1
2
1-3
0
L
INV
INV
INV
9
1-1
0
8
Number of panels
15483
Total DC power
8.283 MWp
PV Field Orientation
South Azimuth : 20.27° Tilt : 10°
Panels setup
3 in Portrait
Distance between rows
2.20 m
Pitch distance
8.95 m
1-9
7
1-2
6
1-8
1-2
5
INV
INV
1
1-2
INV
INV
1-1
1-2
INV
INV
322
1-2
INV
INV
E
W INV
INV
1-3
1-3
1-7
1-2
4
Permanent Road INV
1-2
3
Tra nsfo
INV
1-2
2
INV
T
1-6
rme r
INV
1-5
Non - permanent Road
1533
INV
INV
1-2
1-2
1
0
INV
INV
INV
Rijplaten
1-1
9
1-1
8
INV
INV
1-4
1-3
Wire mesh fence
1-1
7
BRUx-x INV
DC / AC inverter Huawei SUN2000-185KTL-H1 1-1
6
INV
1-2
Transformer station - 1x6600kVA ( UAG01 ) INV
INV
1-1
5
Solar panel - Suntech STP535S-C72/Pmh+ - 535Wp
1-1
4
INV
INV
1-1
Client's station
1-1
3
Handtekening
Revisie
Datum
Omschrijving
1.1 1.2 1.3 1.4 1.5
25-01-2021 10-05-2021 17-06-2021 29-06-2021 07-07-2021
Relocation of some solar modules. Status Design Details for position of inverters, transformer and gravel paths. New information - Outdated Layout New Design with definitive type of modules Final Layout Design
Getekend
V.M.
Gezien
R.B.
Versie
1.5
Datum
20-10-2020
Datum
20-10-2020
Schaal
1:12.5 ( A0 )
V.M. V.M. V.M. V.M. H.R.
Status tekening
T 1547
Locatie
Karakter Energie - Venlo Main
Entr
Kalifornië Venlo
Layout Drawing - LOT 5
anc
e
Opdrechtgever
South Orientation
Karakter Energie PV nummer
L
L 966
983
Design
PA200263
TekenIngnr.
Blad
01
Deze tekening is het eigendom van ProfiNRG
Karakter Energie Venlo – Tables cross section design
Minimum distance between tables ( East- West ) is 700mm
Minimum distance between tables ( South ) is 1600 mm
≥
Alberts & Kluft
NORTH
2111
2111
+2000
5
5
2111
2111
5
5
2111
2111
3 PV
10°
10°
3 PV
870 Ground level
±50 mm
870
±50 mm
+870
+0
?*
* Final minimal depth of studs and possible need of pre-drilling has to be defined by SADEFcustomer and his qualified geologist. In case of terrain irregularity, extra pile length could be needed.
-?
12708 A
B
C
D E
F
G
H
SECTION VIEW
2111
NORTH
5
+2000
2111 5 2111 10°
3 PV
870
±50 mm
+870
?*
Ground level
+0
* Final minimal depth of studs and possible need of pre-drilling has to be defined by SADEFcustomer and his qualified geologist. In case of terrain irregularity, extra pile length could be needed.
-?
ProfiNRG Venlo Section views
6254
A
B
C
D
This structure is valid for the following tolerances of the modules Trinasolar TSM-DEG17M.20(II): - tolerances on the length and width are ± 2mm - tolerance on the thickness is ± 0.5mm
Tekla Structures
SECTION VIEW
This plan cannot be used for the final building site layout of piles, frames or tables. Only the specific SADEF "Structural drawing" may be used to prepare or realize the montage of the SADEF-frame. It is the entire responsability of the SADEF customer to verify the validity and the completeness of the attached data sheet relating to the applied solar panel. It is also the entire responsability of the SADEF customer to verify the compatibility, the panel spacing and the loading capacity of the used solar panels and its fixing to the corresponding SADEF steel frame. The tolerance on the overall PV panel dimension (measured in length direction of table) may not exceed +2mm,-2mm. Production of the SADEF steel frame will only be launched after approval by the SADEF customer on the content of these plans and attachted documents. The layout of the solar tables on the terrain should be done in such a way, that there is always a minimal distance of 10 cm between the steel structures of adjacent tables. In case of a terrain with more than 10% slope, the minimal distance (in cm) should be equal to the slope of the terrain (in %). E.g. 20% terrain slope --> 20cm minimal distance between tables. Standard irregularity in flatness in East-West direction is +/-5cm.
If irregularity (between the 2 ends of table) is more than 5cm, the SADEF customer clearly has to specify the maximum irregularity before approval of the global drawings. The chosen surface treatment of the steel frame is supposing no significant water accumulation on the terrain surface. It is considered that the ground will absorb all rain water. Eventual consequences on the steel structure due to water accumulation or underground waterstream will be the full responsibility of the SADEF customer. Grounding of the installation is the responsibility of the SADEF customer. Grounding of PV-modules is voestalpine SADEF responsibility. The –by the customer- approved voestalpine Sadef documents (drawings & design data) will be prior to all received information from e.g. the voestalpine Sadef customer. The content of the documents "Design data", and "Special conditions for components in solar frames (encl. A)" in enclosure is to be fully taken into account ! This print and the information contained here on is confidential disclosure. The subject matter of which is property of SADEF N.V.
The structure is designed for a terrain without soil settlements or soil sagging. If soil settlements would occur, it is the full responsibility of the Sadef customer to take the necessary measures to avoid damage of the steel structure or PV panels.
This structure is valid for maximal terrain slope in E-W / N-S direction: 3% / flat In case of higher terrain slope, the customer has to do necessary earth movement in order to respect the given slope limits Project Reference:
ProfiNRG Venlo Subject:
Project Start Date:
09/10/2***
ProfiNRG Object:
SOLAR STRUCTURES
plotted 09.02.2021
OFFER This drawing must be printed on paper size not less than A3. 1
A
Offer-New Panel
REV. NO.
REV.
REVISION DESCRIPTION
SteelGrade : S390Gd+Z
09.02.2021 REV. DATE
Unless different mentioned
Welding :
BoltGrade : 8.8, Unless different mentioned
4
, Unless different mentioned
Projection :
Scale:
1:40
G[04] Section views Client:
SO20136733 ProfiNRG Venlo v03
Preliminary drawing
Drawn by:
WN
Phone: +32 (0)51 261 211
Telefax: +32 (0)51 261 301
voestalpine Sadef nv
Checked by: E-Mail: project@sadef.be
Internet: www.sadef.be
PROJECT NUMBER:
SO20136733 DRAWING NO. + REVISION NO.:
G[04]
- A
SUN2000-185KTL-H1 Smart String Inverter
Efficiency
9 MPP Trackers
99.0% Max. Efficiency
String-level Management
Smart I-V Curve Diagnosis Supported
MBUS Supported
Fuse Free Design
Surge Arresters for DC & AC
IP66 Protection
Efficiency Curve
Circuit Diagram +
MPPT1
+ -
L1 L2 L3 PE
+ +
Output Filter
MPPT2
-
EMI Filter
+
MPPT3
+
-
DC Switch 1
SPD
+
MPPT4
+ + +
MPPT5
-
EMI Filter
+
MPPT6
+ -
-
DC Switch 2
SPD
+
MPPT7
+ + +
MPPT8
+
Load
MPPT9
+ -
-
Current Sensor
DC Switch 3
SPD
DC/AC Inverter
Output Relay
SPD
SUN2000-185KTL-H1
Technical Specifications Efficiency Max. Efficiency
99.03%
European Efficiency
98.69%
Input Max. Input Voltage
1,500 V
Max. Current per MPPT
26 A
Max. Short Circuit Current per MPPT
40 A
Start Voltage
550 V
MPPT Operating Voltage Range
500 V ~ 1,500 V
Nominal Input Voltage
1,080 V
Number of Inputs
18
Number of MPP Trackers
9
Output Nominal AC Active Power
185,000 W @25°C, 175,000 W @40°C
Max. AC Apparent Power
185,000 VA
Max. AC Active Power (cosφ=1)
185,000 W
Nominal Output Voltage
800 V, 3W + PE
Rated AC Grid Frequency
50 Hz / 60 Hz
Nominal Output Current
134.9 A @25°C, 126.3 A @40°C
Max. Output Current
134.9 A
Adjustable Power Factor Range
0.8 LG ... 0.8 LD
Max. Total Harmonic Distortion
<3%
Protection Input-side Disconnection Device
Yes
Anti-islanding Protection
Yes
AC Overcurrent Protection
Yes
DC Reverse-polarity Protection
Yes
PV-array String Fault Monitoring
Yes
DC Surge Arrester
Type II
AC Surge Arrester
Type II
DC Insulation Resistance Detection
Yes
Residual Current Monitoring Unit
Yes
Communication Display
LED Indicators, Bluetooth/WLAN + APP
USB
Yes
MBUS
Yes
RS485
Yes
General Dimensions (W x H x D)
1,035 x 700 x 365 mm (40.7 x 27.6 x 14.4 inch)
Weight (with mounting plate)
84 kg (185.2 lb.)
Operating Temperature Range
-25°C ~ 60°C (-13°F ~ 140°F)
Cooling Method
Smart Air Cooling
Max. Operating Altitude without Derating
4,000 m (13,123 ft.)
Relative Humidity
0 ~ 100%
DC Connector
Staubli MC4 EVO2
AC Connector
Waterproof Connector + OT/DT Terminal
Protection Degree Topology
IP66 Transformerless
Standard Compliance (more available upon request) Certificate
EN 62109-1/-2, IEC 62109-1/-2, IEC 62920, EN 50530, IEC 62116, IEC 60068, IEC 61683, IEC 61727, IEC 62910, P.O. 12.3, RD 1699, RD 661, RD 413, RD 1565, RD 1663, UNE 206007-1, UNE 206006
STS-6000K-H1
Simple
Efficient
Prefabricated and pre-tested, no internal cabling needed onsite Compact 20’ HC container design for easy transportation
Eco-design transformer suitable for all Lower self-consumption for higher yields
Smart
Reliable
Real-time monitoring of transformer, LV and MV switchgear 0.2% high precision of LV electricity parameters collection Remote control of ACB and MV Circuit Breaker
Robust design against harsh environments Innovative cooling design, high availability and easy maintenance Comprehensive tests from components, device to solution
Schematic Diagram
Transformer
LV Switchgear
MV Switchgear
SOLAR.HUAWEI.COM
STS-6000K-H1, Ecodesign
Technical Specifications Input Available Inverters
SUN2000-185KTL-H1 6,300 kVA @40℃ / 5,760 kVA @50℃1
AC Power Max. Inverters Quantity
36
Rated Input Voltage
800 V
Max. Input Current at Nominal Voltage
2,428 A x 2
LV Main Switches
ACB (2500 A / 800 V / 3P, 2*1 pcs), MCCB (250 A / 800 V / 3P, 2*18 pcs)
Output Rated Output Voltage
10 kV
20 kV
22 kV
30 kV
33 kV
35 kV
34.5 kV
Frequency
50 Hz
50 Hz
50 Hz
50 Hz
50 Hz
50 Hz
60 Hz
Transformer Type
Oil-immersed, Conservator Type
Tappings
± 2 x 2.5%
Transformer Oil Type
Mineral Oil
Transformer Vector Group
Dy11-y11
Minimum Peak Efficiency Index
In accordance with EN 50588-1
Transformer Load Losses
49.7 kW
49.7 kW
49.7 kW
49.7 kW
49.7 kW
49.7 kW
41 kW
Transformer No-load Losses
4.8 kW
4.8 kW
4.8 kW
4.8 kW
4.8 kW
4.8 kW
5.8 kW
Impedance(HV-LV1, LV2)
7.5% (0 ~ +10%) @6,300 kVA
MV Switchgear Type MV Switchgear Configuration
SF6 Gas Insulated, 3 Feeders
CVC or CCV
DVC or DCV Dry type transformer, 5 kVA, Dyn11
Auxiliary Transformer
400 / 230 Vac
Output Voltage of Auxiliary Transformer
220 / 127 Vac
Protection Transformer Monitoring & Protection
Oil level, oil temperature, pressure and buchholz
Protection Degree of MV & LV Room
IP 54
Internal Arcing Fault MV Switchgear
IAC A 20 kA 1s
MV Relay Protection
50/51, 50N/51N
MV Surge Arrester
Equipped
LV Overvoltage Protection
Type I+II
General Dimensions (W x H x D)
6,058 x 2,896 x 2,438 mm (20’ HC Container)
Weight
< 22 t
Operating Temperature Range
-25℃ ~ 60℃2 (-13°F ~ 140°F)
Relative Humidity
0% ~ 95%
Max. Operating Altitude
2,000 m
Enclosure Color
Applicable Standards
RAL 9003
IEC 62271-202, EN 50588-1, IEC 60076, IEC 62271-200, IEC 61439-1
Features Auxiliary Transformer(50 kVA, Dyn11)
Optional3
1.5 kVA UPS
Optional3
Updated to CVC or CCV MV Switchgear
Optional3
IMD
Optional3
STS Interlocking
Optional3
1 - More detailed AC power of STS, please refer to the de-rating curve. 2 - When ambient temperature ≥55℃, awning shall be equipped for STS on site by customer. 3 – Extra expense needed for optional features which standard product doesn’t contain.
SOLAR.HUAWEI.COM
2,500 m
Ultra-V Series
530-550W STPXXXS - C72/Pmh+
144 HALF-CELL BIFACIAL MODULE
Features
21.3%
Weak light
2400 Pa 5400 Pa
High module conversion efficiency Module efficiency up to 21.3% achieved through advanced cell technology and manufacturing process
PID Resistant
High PID resistant Advanced cell technology and qualified materials lead to high resistance to PID
Excellent weak light performance More power output in weak light condition, such as haze, cloudy, and morning
Lower operating temperature Lower operating temperature and temperature coefficient increases the power output
Extended load tests Module certified to withstand front side maximum static test load (5400 Pascal) and rear side maximum static test loads (2400 Pascal) *
Withstanding harsh environment Reliable quality leads to a better sustainability even in harsh environment like desert, farm and coastline
**
***
Certifications and standards: IEC 61215, IEC 61730, conformity to CE
Trust Suntech to Deliver Reliable Performance Over Time
Half-Cell +Bifacial
• World-class manufacturer of crystalline silicon photovoltaic modules • Unrivaled manufacturing capacity and world-class technology • Rigorous quality control meeting the highest international standards: ISO 9001, ISO 14001 and ISO17025 • Regular independently checked production process from international accredited institute/company • Tested for harsh environments (salt mist, ammonia corrosion and sand blowing testing: IEC 61701, IEC 62716, DIN EN 60068-2-68)**** • Long-term reliability tests • 2 × 100% EL inspection ensuring defect-free modules
MBB technology decreases the distance between bus bars and finger grid line which is benefit to power increase. Half-cell aims to eliminate the cell gap to increase module efficiency.
Industry-leading Warranty based on nominal power
IP68 Rated Junction Box
Warranted Power Output
100% 98%
90%
84.95% 80%
1
• 98% in the first year, thereafter, for years two (2) through thirty (30), 0.45% maximum decrease from Industr y leadi ng line MODULE’s nominal power output ar war 10 10 ranty per year, ending with the 84.95% in the 30th year after the defined 25 WARRANTY STARTING DATE.***** 10 30 • 12-year product warranty • 30-year linear performance warranty
The Suntech IP68 rated junction box ensures an outstanding waterproof level, supports installations in all orientations and reduces stress on the cables. High reliable performance, low resistance connectors ensure maximum output for the highest energy production.
* Please refer to Suntech Standard Module Installation Manual for details. ** Suntech reserves the right to the final interpretation of the warranty by Munich Re. ***WEEE only for EU market. **** Please refer to Suntech Product Near-coast Installation Manual for details. ***** Please refer to Suntech Product Warranty for details.
©Copyright 2020 Suntech Power
www.suntech-power.com
IEC-STP-HIPerforma-NO1.01-Rev 2020
Electrical Characteristics STC
STPXXXS-C72/Pmh+
Maximum Power at STC (Pmax)
550W
545W
540W
535W
530W
Optimum Operating Voltage (Vmp)
42.05V
41.87V
41.75V
41.57V
41.39V
Optimum Operating Current (Imp)
13.08A
13.02A
12.94A
12.87A
12.81A
Open Circuit Voltage (Voc)
49.88V
49.69V
49.54V
49.39V
49.24V
Short Circuit Current (Isc)
14.01A
13.96A
13.89A
13.83A
13.76A
Module Efficiency
21.3%
21.1%
20.9%
20.7%
20.5%
Operating Module Temperature
-40 °C to +85 °C
Maximum System Voltage
1500 V DC (IEC)
Maximum Series Fuse Rating
25 A
Power Tolerance
0/+5 W
STC: lrradiance 1000 W/m2, module temperature 25 °C, AM=1.5; Tolerance of Pmax is within +/- 3% .
NMOT
STPXXXS-C72/Pmh+ 415.0W
411.5W
408.0W
404.3W
400.6W
Optimum Operating Voltage (Vmp)
38.9V
38.7V
38.6V
38.4V
38.2V
Optimum Operating Current (Imp)
10.67A
10.63A
10.58A
10.53A
10.47A
Open Circuit Voltage (Voc)
46.9V
16.7V
46.5V
46.4V
46.3V
Short Circuit Current (Isc)
11.22A
11.18A
11.13A
11.08A
11.02A
Model Number a b Rated Max Power(Pmax) c Output Tolerance d Current at Pmax(Imp) e Voltage at Pmax(Vmp) All technical data at standard test condition AM=1.5 E=1000W/m Tc=25℃
Short-Circuit Current(Isc) Open-Circuit Voltage(Voc) Max Series Fuse Rating Max System Voltage Module Application
Wuxi Suntech Power Co.,Ltd. Add: No.16 Xinhua Road, New District Wuxi, China 214028 Customer Service Hot Line: +86 400 8888 009 Fax:+86 510 8534 3321
f g h iClass A
Made in China
TL-CABLE01
Maximum Power at NMOT (Pmax)
NMOT: Irradiance 800 W/m2, ambient temperature 20 °C, AM=1.5, wind speed 1 m/s.
Electrical Characteristics with Different Rearside Power Gain(Reference to 540 W Front) 5%
15%
25%
Maximum Power at STC (Pmax)
567W
621W
675W
Optimum Operating Voltage (Vmp)
41.8V
41.8V
41.9V
Optimum Operating Current (Imp)
13.59A
14.88A
16.18A
Open Circuit Voltage (Voc)
49.5V
49.5V
49.6V
Short Circuit Current (Isc)
14.48A
15.86A
17.24A
Module Efficiency
21.9%
24.0%
26.1%
Current-Voltage & Power-Voltage Curve (550S) 16
600 550
14
Temperature Characteristics
500
12
42 ± 2 °C
Temperature Coefficient of Pmax
-0.36%/°C
Temperature Coefficient of Voc
-0.304%/°C
Temperature Coefficient of Isc
0.050%/°C
450 400
10
Current (A)
Nominal Module Operating Temperature (NMOT)
Mechanical Characteristics
350
8
300 250
6
200
4
150 100
2
50
0
Solar Cell
Monocrystalline silicon 182 mm
No. of Cells
144 (6 × 24)
Dimensions
2279 × 1134 × 35 mm (89.7 × 44.6 × 1.4 inches)
Weight
32.8 kgs (72.3 lbs.)
Front and Back Glass
2.0+2.0 mm (0.079+ 0.079inches) semi-tempered glass
Frame
Anodized aluminium alloy
Junction Box
IP68 rated (3 bypass diodes)
Output Cables
4.0 mm2, Portrait: (-)350 mm and (+)160 mm in length Landscape: (-)1400 mm and (+)1400 mm in length or customized length
Connectors
MC4 EVO2, Cable 01S
Refer. Bifaciality Factor
(70 ± 5)%
Power (W)
Rearside Power Gain
0 0
10
20
30
40
50
Votage (V) 1000 W/m2
800 W/m2
600 W/m2
400 W/m2
200 W/m2
Dealer information
Packing Configuration Container Pieces per pallet
40’ HC 31
Pallets per container
20
Pieces per container
620
Packaging box dimensions Packaging box weight
2310×1130×1245 mm 1080 kg
Information on how to install and operate this product is available in the installation instruction. All values indicated in this data sheet are subject to change without prior announcement. The specifications may vary slightly. All specifications are in accordance with standard EN 50380. Color differences of the modules relative to the figures as well as discolorations of/in the modules which do not impair their proper functioning are possible and do not constitute a deviation from the specification.
IEC-STP-Vem-NO1.01-Rev 2014 ©Copyright 2020 Suntech Power
www.suntech-power.com
IEC-STP-HIPerforma-NO1.01-Rev 2020
SECTION A-A'
Non-permanent construction roads Those roads can be built directly on the topsoil layer. Removing the humus layer is not required. We propose to compact the loosened topsoil by a roller compactor on all construction roads built later on before further activities. We recommend building up this plane with a well compacted sand-gravel mixture or crushed concrete 0/32. To separate the materials from the topsoil, use a simple non-woven geotextile combined with a geogrid. This material should have a thickness of approx. 0.20 m and be compacted in one layer.
350
PERMANENT CONSTRUCTION ROAD
Permanent construction roads
Ground level ( - 0 )
GRAVEL SAND / MENGGRANULAAT
40
For construction roads, able to bear the loads from heavy goods vehicles, the vegetation cover and 0.2 m of the underlying topsoil need to be taken away completely and a plane with a homogeneous slope of > 3° needs to be established. On this plane, a simple geotextile combined with a geogrid has to be installed. We recommend building up this plane with a well compacted sand-gravel mixture or crushed concrete 0/32. This material should have a thickness of approx. 0.4 m and has to be compacted in two layers. This filling should have a degree of compaction of 98% standard Proctor density.
Geotextile combined with Geogrid 80
EARTH/SOIL
15
10
General instructions
MV Cables 3x1x95 mm² ( trefoil )
- LV cables will be installed at 60cm depth with warning red tape above them. - LV cables will be installed with a distance of 12,5cm between them. - MV cables will be installed at 80cm depth with a PVC protective sheet above them. - All the cables will be installed in a layer ( 5cm ) of clean sand and will be cover with a layer ( 10cm ) of clean sand as well. - The soil that will be used as a backfill needs to be clean of dirt and stones. In the trenches below the permanent roads, the topsoil layer ( 20 cm ) cannot be used as a backfill. - The gravel sand / menggranulaat road needs to be compacted according to the requirements. - Distances are indicated in cm.
PVC Protection sheet for MV cables ( 30cm wide )
SECTION B-B' 350
PERMANENT CONSTRUCTION ROAD Ground level ( - 0 )
GRAVEL SAND / MENGGRANULAAT
EARTH/SOIL
40
Geotextile combined with Geogrid 60
BACKFILL SOIL CLEAN OF DIRT AND STONES 12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
20
12.5
12.5
12.5
12.5
35
12.5
12.5
12.5
15
EARTH/SOIL
10
GRAVEL SAND / MENGGRANULAAT
Warning Tape (red) above the LV cables LV cables,Al - 3x120 mm²
CLEAN SAND
250
MV Cables 3x1x95 mm² ( trefoil )
PVC Protection sheet for MV cables ( 30cm wide )
SECTION C-C' Handtekening
Revisie
Datum
Omschrijving
Getekend
V.M.
Gezien
R.B.
Versie
1.0
Datum
07-07-2021
Datum
07-07-2021
Schaal
n/a
350
NON- PERMANENT CONSTRUCTION ROAD GRAVEL SAND / MENGGRANULAAT
Ground level ( - 0 )
Geotextile combined with Geogrid
BACKFILL SOIL CLEAN OF DIRT AND STONES 12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
Warning Tape (red) above the LV cables 12.5
12.5
12.5
15
LV cables,Al - 3x120 mm² 250
Design Locatie
Karakter Energie - Venlo
Kalifornië Venlo
LOT 5
55
60
10
20
Status tekening
Opdrechtgever
Maintenance roads & Cross sections
Karakter Energie PV nummer
PA200263
TekenIngnr.
Blad
01
Deze tekening is het eigendom van ProfiNRG
2.89
Huawei STS Transformer station
6.05
2.44
Front view
6.05
Top view