CConstaterende datDen Helder
Koppel je AI →
Document · PDF

Z2025-03-0036 - D2025-07-000694 - Datasheet batterijsysteem_datasheet 20C2H1600K.pdf.pdf

Gemeenteraad 9 februari 2026, gemeente Den HelderBij agendapunt: 16: Voorstel tot advies over omgevingsvergunning energieopslagsysteem vlakbij Luchthavenweg 28T (Heldair II).1.139 woorden

Open het PDF bij iBabs ↗Naar de vergadering →

Tekst van het document

Uit het bestand gehaald, zonder opmaak, tabellen en afbeeldingen

PowerCombo-20C2H1600K Resilient, Reliable, and Quick Delivery Liquid Cooling Energy Station

PowerCombo-20C2H1600K

PowerCombo, a high-performance, all-in-one, contain-

PowerCombo-20C2H1600K, with capacity of

erized battery energy storage system developed by

3,008kWh@20ft, is ideal for mostly utility and C&I

Cubenergy, provides C&I users with the intelligent and

applications, such as renewable energy power plant

reliable solution to optimize energy efficiency and

supplement, factories, buildings, etc. The integrated and

resilience. As the leading BESS product, PowerCombo is

easy-to-install BESS can be easily connected and

certificated by UL1973, UL9540A, UL9540, IEC62619, CE,

matched with the equipment, while the advanced BMS

UN38.3, complied with IEC62933, IEC62056, NFPA855,

and cloud-based operation platforms bring superior

provides secure, reliable and safe power supply.

interaction experience for users.

Application Smooth New Energy Output Voltage, Frequency Support, Frequency Modulation Peak Valley Arbitrage Demand Management Construction of Microgrid

01

PowerCombo-20C2H1600K

System Topology

C&I

Grid

Power Station

Step-up Transformer

PCS-1#

PCS-2#

PCS-3#

PCS-4#

PCS-5#

BESS controller

PCS-6#

PCS-7#

PCS-8#

FFS

Auxiliary Power 1#String

2#String

3#String

4#String

5#String

6#String

7#String

8#String

Air conditioning

More Energy

All-in-one Design

Simple O&M

Safe & Reliable

Pack-level Optimization String-level Optimization

AC/DC All-in-one Design Reducing Initial Investment

No periodic balancing No experts site visit

Modular Design High Availability

PowerCombo-20C2H1600K

02

Product Layout

PCS(Inverter)

Battery String

BESS Controller Air Conditioner

HVU Panel AC Power Output

HVU

FFS

Product Model Definition

20C2H1600K-8LS376-8LP47 Container Size

Minimum Discharge Hour

AC Power

Quantity of Code of Quantity of Battery String Battery String Pack per String

47kWh Pack

Product Configuration Product Model

03

Battery String Qty String Type

Nominal Capacity

DC Voltage Range

Grid-connected Max Rated Voltage

Dimensions (WDH mm)

20C2H1600K

LS376

8

3,008kWh

1075.2V~1363.2V

690V

6,058x2,438x2,896mm

20C1H1000KLS

LS376

8

1,880kWh

672V~852V

400V

6,058x2,438x2,896mm

20C2H1000KLS

LS376

8

2,256kWh

806.4V~1022.4V

400V

6,058x2,438x2,896mm

PowerCombo-20C2H1600K

System Technical Specifications Item

20C2H1600K

20C1H1000KLS

20C2H1000KLS

DC Data Battery chemistry

Lithium Iron Phosphate (LFP)

Cell life cycle

70% Retention with 8,000 Cycles @ 0.5C 25℃

Cell spec

3.2V/306Ah

String configuration

1P384S

1P240S

1P288S

Number of strings

8

8

8

DC rated energy capacity

3,008kWh

1,880kWh

2,256kWh

Rated voltage

1,228.8V

768V

921.6V

Voltage range

1,075.2V~1,363.2V

672V~852V

806.4V~1022.4V

BMS communication interface

RS485, Ethernet

BMS communication protocol

Modbus RTU, Modbus TCP

AC Data

Standard Output

Rated AC Power

1,600kW

1,000kW

1,000kW

Maximum AC power

1,760kW

1,100kW

1,100kW

Rated voltage

690V

400V

400V

Grid voltage range

586.5~759V(Optional)

340~440V(Optional)

340~440V(Optional)

AC rate of current

1,338.8A

1,443.4A

1,443.4A

Output THDi

<3%

AC PF

-1~+1

AC output

3W+PE

30.1t

30.4t

General Data Dimension w/o clearances (L*W*H)

6,058x2,438x2,896mm

Weight of the whole system

31t

Degree of protection

IP54

Operating temperature range

-20~40℃(Max.-30~55℃)

Relative humidity

0~95% (non-condensing)

Max working altitude

2,000m/6,562feet(non-derating)

Cooling concept of DC hatch

Liquid Cooling and Dehumidification system

Fire fighting system

FK-5-1-12

Communication interfaces

RS485, Ethernet

Certificates

UL9540, IEC62933, UN3536, CE MARK by TÜV Rheinland

PowerCombo-20C2H1600K

04

Key Components Battery String

0.5C Charge/Discharge; Power supply can be single battery string or parallel battery strings; Easy configuration and maintenance.

Item

20C2H1600K

20C1H1000KLS 20C2H1000KLS

Battery module

LS376

LS376

LS376

Pack QTY

8

5

6

Rated capacity

376.01kWh

235.01kWh

282.01kWh

Rated voltage

1,228.8V

768V

921.6V

DC voltage range

1,075.2V~1,363.2V 672V~852V

Pack

153.6V/306Ah@1P48S

Communication

Ethernet, CAN, RS485

Lifespan

>8,000 cycles@0.5C, 25℃

Dimensions (W×D×H)

862×1,100×2,228mm

Weight

2,540kg

Certifications

UL1973, UL9540A, IEC62619, UN38.3

1,588kg

806.4V~1,022.4V

1,905kg

Power Conversion System

Single-stage three-level modularization; Multi-branch input to reduce battery series and parallels connection; One-to-one Management of Battery string and PCS.

Item

20C2H1600K

20C1H1000KLS/202H1000KLS

DC voltage range

1000~1,500V

600~1,500V

Maximum DC current

224.5A * 8

233.8A * 8

Rated output power

200kW * 8

125kW * 8

Rated grid voltage

690V, 3W+PE

400V, 3W+PE

Grid voltage range

586.5~759V(Optional)

340~440V(Optional)

Grid frequency

50Hz/60Hz

50Hz/60Hz

Max AC current

184.1A * 8

198.4A * 8

AC PF

-1~+1

-1~+1

Weight

100kg * 8

98kg * 8

Certifications

UL 1741, IEEE 1547, EN50549, IEC62477, IEC 61000

* Data for 690V output version

GridPoint Controller(GPC)

All-round signal collection; Comprehensive logical control; Multilevel electric & control protection; Intelligentize Sub-System management ; Quick and Simple Configuration and Connect with third-part SCADA and EMS.

05

PowerCombo-20C2H1600K

Item

Data

Power interface

AC400V/DC24V

Communication and Relay

Modbus RTU、Modbus TCP

Power backup for Monitoring

Reseverd UPS connection

Control mode with EMS

Time-of-use, Peak shaving, Flexibility service Renewable smoothing, Grid-Forming

BMS with Real-time Active Balance PCS

Environment Control System

Fire Extinguishing System

Auxiliary equipment

Battery String Bus

System Protection Strategy

Alarm Management

Error Disconnection Control

SOE

Dispatch Strategy

GPC

CMU

SOC/SOH

Over value

Current Leakage

Insulation Detection

Process Chain

Online Update

Balance Logic Control

Alarm Management

Battery String DC Bus Voltage

Battery String DC Bus Current

Data Calculation and Record

Battery String Protection Strategy

BMU

Cell

Cell 1

......

Cell Voltage

Active Balance

Cable Temperature

CANBUS

Module Voltage

Offline Check

Cell N

Cell 1

BMU

......

Cell N

Cell 1

......

Cell N

Cell 1

......

Cell N

CMU

Cell Voltage Measurement Accuracy

±2.5 mV

Battery String Voltage Measurement Range

100~1,500V

Cell Voltage Monitoring Interval

≤500ms

Battery String Voltage Measurement Accuracy

±1%

Cell Temperature Measurement Accuracy

±2℃

Battery String Voltage Monitoring Interval

≤200ms

Cell Temperature Measurement Interval

≤3s

Battery String Current Measurement Range

±300A

Cell Current Balance

Active Balance,5A MAX

Battery String Current Measurement Accuracy

≤1%

Cell Voltage Measurement Range

1~5 V

Battery String Current Monitoring Interval

≤50ms

Over-current Protection

250A/1s

SOC Calculation Accuracy

≤8%

Short-Circuit Protection

500A/10ms

Input Insulation Resistance

≥10MΩ,1,000VDC

PowerCombo-20C2H1600K

06

Product dimensions and physical appearance in this brochure are nominal and are provided for the convenience of our customers. Cubenergy reserves the right to make changes from time to time, without prior notification, which may change the dimensions and physical appearance shown.

We therefore recommend you to consult with a Cubenergy sales representative before your purchase. ©2024 Cubenergy. All rights reserved.

www.cubenergy.com info@cubenergy.com Houston, TX, US

De tekst is automatisch uit het bestand gehaald en kan afwijken van het origineel (kolommen, tabellen en koppen lopen door elkaar). Het officiële stuk bij iBabs is leidend. Bron: https://gemeenteraad.denhelder.nl/api/v1/meetings/2449/documents/26330