Z2025-03-0036 - D2025-07-000694 - Datasheet batterijsysteem_datasheet 20C2H1600K.pdf.pdf
Tekst van het document
PowerCombo-20C2H1600K Resilient, Reliable, and Quick Delivery Liquid Cooling Energy Station
PowerCombo-20C2H1600K
PowerCombo, a high-performance, all-in-one, contain-
PowerCombo-20C2H1600K, with capacity of
erized battery energy storage system developed by
3,008kWh@20ft, is ideal for mostly utility and C&I
Cubenergy, provides C&I users with the intelligent and
applications, such as renewable energy power plant
reliable solution to optimize energy efficiency and
supplement, factories, buildings, etc. The integrated and
resilience. As the leading BESS product, PowerCombo is
easy-to-install BESS can be easily connected and
certificated by UL1973, UL9540A, UL9540, IEC62619, CE,
matched with the equipment, while the advanced BMS
UN38.3, complied with IEC62933, IEC62056, NFPA855,
and cloud-based operation platforms bring superior
provides secure, reliable and safe power supply.
interaction experience for users.
Application Smooth New Energy Output Voltage, Frequency Support, Frequency Modulation Peak Valley Arbitrage Demand Management Construction of Microgrid
01
PowerCombo-20C2H1600K
System Topology
C&I
Grid
Power Station
Step-up Transformer
PCS-1#
PCS-2#
PCS-3#
PCS-4#
PCS-5#
BESS controller
PCS-6#
PCS-7#
PCS-8#
FFS
Auxiliary Power 1#String
2#String
3#String
4#String
5#String
6#String
7#String
8#String
Air conditioning
More Energy
All-in-one Design
Simple O&M
Safe & Reliable
Pack-level Optimization String-level Optimization
AC/DC All-in-one Design Reducing Initial Investment
No periodic balancing No experts site visit
Modular Design High Availability
PowerCombo-20C2H1600K
02
Product Layout
PCS(Inverter)
Battery String
BESS Controller Air Conditioner
HVU Panel AC Power Output
HVU
FFS
Product Model Definition
20C2H1600K-8LS376-8LP47 Container Size
Minimum Discharge Hour
AC Power
Quantity of Code of Quantity of Battery String Battery String Pack per String
47kWh Pack
Product Configuration Product Model
03
Battery String Qty String Type
Nominal Capacity
DC Voltage Range
Grid-connected Max Rated Voltage
Dimensions (WDH mm)
20C2H1600K
LS376
8
3,008kWh
1075.2V~1363.2V
690V
6,058x2,438x2,896mm
20C1H1000KLS
LS376
8
1,880kWh
672V~852V
400V
6,058x2,438x2,896mm
20C2H1000KLS
LS376
8
2,256kWh
806.4V~1022.4V
400V
6,058x2,438x2,896mm
PowerCombo-20C2H1600K
System Technical Specifications Item
20C2H1600K
20C1H1000KLS
20C2H1000KLS
DC Data Battery chemistry
Lithium Iron Phosphate (LFP)
Cell life cycle
70% Retention with 8,000 Cycles @ 0.5C 25℃
Cell spec
3.2V/306Ah
String configuration
1P384S
1P240S
1P288S
Number of strings
8
8
8
DC rated energy capacity
3,008kWh
1,880kWh
2,256kWh
Rated voltage
1,228.8V
768V
921.6V
Voltage range
1,075.2V~1,363.2V
672V~852V
806.4V~1022.4V
BMS communication interface
RS485, Ethernet
BMS communication protocol
Modbus RTU, Modbus TCP
AC Data
Standard Output
Rated AC Power
1,600kW
1,000kW
1,000kW
Maximum AC power
1,760kW
1,100kW
1,100kW
Rated voltage
690V
400V
400V
Grid voltage range
586.5~759V(Optional)
340~440V(Optional)
340~440V(Optional)
AC rate of current
1,338.8A
1,443.4A
1,443.4A
Output THDi
<3%
AC PF
-1~+1
AC output
3W+PE
30.1t
30.4t
General Data Dimension w/o clearances (L*W*H)
6,058x2,438x2,896mm
Weight of the whole system
31t
Degree of protection
IP54
Operating temperature range
-20~40℃(Max.-30~55℃)
Relative humidity
0~95% (non-condensing)
Max working altitude
2,000m/6,562feet(non-derating)
Cooling concept of DC hatch
Liquid Cooling and Dehumidification system
Fire fighting system
FK-5-1-12
Communication interfaces
RS485, Ethernet
Certificates
UL9540, IEC62933, UN3536, CE MARK by TÜV Rheinland
PowerCombo-20C2H1600K
04
Key Components Battery String
0.5C Charge/Discharge; Power supply can be single battery string or parallel battery strings; Easy configuration and maintenance.
Item
20C2H1600K
20C1H1000KLS 20C2H1000KLS
Battery module
LS376
LS376
LS376
Pack QTY
8
5
6
Rated capacity
376.01kWh
235.01kWh
282.01kWh
Rated voltage
1,228.8V
768V
921.6V
DC voltage range
1,075.2V~1,363.2V 672V~852V
Pack
153.6V/306Ah@1P48S
Communication
Ethernet, CAN, RS485
Lifespan
>8,000 cycles@0.5C, 25℃
Dimensions (W×D×H)
862×1,100×2,228mm
Weight
2,540kg
Certifications
UL1973, UL9540A, IEC62619, UN38.3
1,588kg
806.4V~1,022.4V
1,905kg
Power Conversion System
Single-stage three-level modularization; Multi-branch input to reduce battery series and parallels connection; One-to-one Management of Battery string and PCS.
Item
20C2H1600K
20C1H1000KLS/202H1000KLS
DC voltage range
1000~1,500V
600~1,500V
Maximum DC current
224.5A * 8
233.8A * 8
Rated output power
200kW * 8
125kW * 8
Rated grid voltage
690V, 3W+PE
400V, 3W+PE
Grid voltage range
586.5~759V(Optional)
340~440V(Optional)
Grid frequency
50Hz/60Hz
50Hz/60Hz
Max AC current
184.1A * 8
198.4A * 8
AC PF
-1~+1
-1~+1
Weight
100kg * 8
98kg * 8
Certifications
UL 1741, IEEE 1547, EN50549, IEC62477, IEC 61000
* Data for 690V output version
GridPoint Controller(GPC)
All-round signal collection; Comprehensive logical control; Multilevel electric & control protection; Intelligentize Sub-System management ; Quick and Simple Configuration and Connect with third-part SCADA and EMS.
05
PowerCombo-20C2H1600K
Item
Data
Power interface
AC400V/DC24V
Communication and Relay
Modbus RTU、Modbus TCP
Power backup for Monitoring
Reseverd UPS connection
Control mode with EMS
Time-of-use, Peak shaving, Flexibility service Renewable smoothing, Grid-Forming
BMS with Real-time Active Balance PCS
Environment Control System
Fire Extinguishing System
Auxiliary equipment
Battery String Bus
System Protection Strategy
Alarm Management
Error Disconnection Control
SOE
Dispatch Strategy
GPC
CMU
SOC/SOH
Over value
Current Leakage
Insulation Detection
Process Chain
Online Update
Balance Logic Control
Alarm Management
Battery String DC Bus Voltage
Battery String DC Bus Current
Data Calculation and Record
Battery String Protection Strategy
BMU
Cell
Cell 1
......
Cell Voltage
Active Balance
Cable Temperature
CANBUS
Module Voltage
Offline Check
Cell N
Cell 1
BMU
......
Cell N
Cell 1
......
Cell N
Cell 1
......
Cell N
CMU
Cell Voltage Measurement Accuracy
±2.5 mV
Battery String Voltage Measurement Range
100~1,500V
Cell Voltage Monitoring Interval
≤500ms
Battery String Voltage Measurement Accuracy
±1%
Cell Temperature Measurement Accuracy
±2℃
Battery String Voltage Monitoring Interval
≤200ms
Cell Temperature Measurement Interval
≤3s
Battery String Current Measurement Range
±300A
Cell Current Balance
Active Balance,5A MAX
Battery String Current Measurement Accuracy
≤1%
Cell Voltage Measurement Range
1~5 V
Battery String Current Monitoring Interval
≤50ms
Over-current Protection
250A/1s
SOC Calculation Accuracy
≤8%
Short-Circuit Protection
500A/10ms
Input Insulation Resistance
≥10MΩ,1,000VDC
PowerCombo-20C2H1600K
06
Product dimensions and physical appearance in this brochure are nominal and are provided for the convenience of our customers. Cubenergy reserves the right to make changes from time to time, without prior notification, which may change the dimensions and physical appearance shown.
We therefore recommend you to consult with a Cubenergy sales representative before your purchase. ©2024 Cubenergy. All rights reserved.
www.cubenergy.com info@cubenergy.com Houston, TX, US