BPS - S Battery Power Station - String Full Outdoor
Custom design based on customer requirements
Oil collection tank included
Made in Europe
Easily transportable by standard truck or OT container
Meins BPS-S is a Power Station, Plug & Play philosophy, designed to connect to a battery container equipped with integrated string inverters. The power capacity is fully customizable, depending on the specifications and capacity of the battery container, with a maximum power capacity of up to 7 MW. It consists of a precast concrete platform equipped with a LV panel and a MV switchgear, as well as a power transformer equipped with oil collection tank and a perimeter fence.
© 2025 Meins. All rights reserved. Subject to change without notice. Version 1.0
BPS - S Battery Power Station - String | Full Outdoor
Technical specifications Transformer Transfomer type / Cooling / Winding AC Power Vector group Voltage ratio / (U m / U AC / U LI)
Hermetically sealed corrugated tank / ONAN / Aluminium MV & LV winding 5200 kVA (40 ºC) Dy11y11 (IT system. TN system on request) 10,5-21 kV (25-50-125 kV) / Secondary: 800-800 V (3,6-10-20 kV) *Depending on the inverter model selected
Frequency / No-load tap changer
50Hz / DETC ± 2 x 2.5%
Maximum no-load / load losses
No load: UE548/2014 TIER 2 / Load: UE548/2014 TIER 2
Ucc % (HV/V1-LV2 / HV-LV1 / HV-LV2) Other features Optional
7% / 7% / 7% DGPT2+PT100, MV bushing type C, filling and drainage valve, lifting lugs, grounding terminal, LV terminal cover Dual primary winding, KNAN
MV switchgear (Outdoor) Insulation type / Rated voltage / (U m / U AC / U LI)
SF6 / 24 kV / (24-50-125 kV). SF6-Free
Nominal current / Short-time current / IAC
630 A / 20 kA/1s / IAC AFLR 20 kA/1s
Configuration Transformer protection device
2R1L (without motorized CB) Self-powered relay (50,51,50N,51N)
Other features
Voltage presence device VOIS+, 1st y 2nd trip coil, manometer, bushing type C, grounding terminals, C1 interlocking at transformer switchgear
Optional
Motorized CB, P1 cross interlocking at line switchgear, cascade control, double cable/phase kit, MV surge arrester, undervoltage coil, voltage presence device Capdis S2+, voltage presence device VOIS R+.
LV panel (Outdoor) ACB - Specification MCCB / Fuse / MCB / RCCB – Specification
2x 2000 A / LSI / 1000 Vac / 85 kA / 3P / Trip coil MCCB: 24x 250 A (not necessary if inverters have self-protection) + 2x 63 A / LSI / 800Vac / 50kA / 3P Fuses: 6x 125 A (SPD) + 3x 80 A (AASS Transformer) MCB-RCCB: As per SLD
Auxiliary transformer Other features Optional
Three phase: 100 kVA, 3x800 V / 3x400+N V, IP00, 50 Hz, up to 1000 m.a.s.l UPS DC/DC 24 Vdc, PLC for signal monitoring, SPD I+II, lighting and socket system Motorized ACB + close coil / undervoltage coil, UPS AC/AC 230 Vac up to 3 kVA, insulation monitoring device, Emergency trip button, pre-installation of customer communications devices and terminals, datalogger PLC and power supply cabling, Grid analyzer 800Vac, U/F relay, unmanaged ethernet switch
Miscellaneous Other features
Oil retention tank, security tools, fire & anti-intrusion detecting system, earthing system, LV cabling & MV cabling with KOZ clamps
Optional
Seismic anchorage pieces, foundation calculation report, precast footing, carbon filter, perimeter fence with key lock and roof, set of handling hooks
General Structure material Dimensions (L x W x H) Weight Operation temperature / Humidity Range Protection rating / Painting colour
Reinforced and vibrated concrete 6385 x 2050 x 2500 mm <22 Tn -15°C ~ 60°C (-13 °F ~ 140 °F) / 0% ~ 95% Transformer, LV panel: IP54 / C4H / RAL 7035 MV switchgear: IP54 / C5M / RAL 7035 Perimeter fence: IPX2 / C4H / RAL 7035 Concrete skid: RAL 7035 *Other RAL upon request
Max. operating altitude Standards
© 2025 Meins. All rights reserved. Subject to change without notice. Version 1.0
2000 m (higher altitude available as optional) REBT, RAT, NEN, VDE, IEC 60076, IEC 61439-1, IEC 62271-200, IEC 62271-202, EN 50588-1