373kWh DC Outdoor Cabinet World-Class Battery Manufacturer
CONTENTS
• Dc cabinet specification • Advantage • Safety design • Product structure • Main component -- Fire protection system
-- Liquid cooling system -- Battery management system -- Battery pack -- Electrical communication system • Process flow • Certificate • Matching PCS model
Spec of 373kWh DC Cabinet
产品类型
Magna-UTL-373
Product category
DC liquid-cooling outdoor cabinet energy storage solution
Rated capacity
372.736kWh@0.5C
Rated output power
180kW
Rated voltage
900-1500Vd.c.
Cell capacity
280Ah
Cell type
LFP
Disposition
1P416S
Maximum discharge current
173A
Maximum charging current
173A
Charging temperature
0~50℃
Discharge temperature
-20~50℃
Communication interface
485/CAN
Cooling mode
Liquid cooling
Waterproof class
IP55
Functional safety
ASIL B
Product weight
≈3850kg
dimension
W1300*D1300*H2373.5mm
Application field
Utility,grid, C&I
Advantage
High security • Active safety fire protection system • Complies with UL 9540A • Complies with NFPA68
Long-life Combined with intelligent liquid cooling control system, of uniform heat dissipation & small battery temperature difference, which guarantees operation in the best temperature range, to extend battery life.
B
Extend easily Intelligent management system, compatible with different converters for a variety of energy storage scenarios
High integration Integrated design, integral transportation, plug&play
C D
A
Safety Design-LFP cell ⚫ High safety LFP system of optimized stability of the anode structure ;
Cathode
⚫ Optimize the ratio of electrolyte to reduce the IR,
Anode
performance ;
⚫ High adhesion and stability, low resistance and temperature rise, safety and long-term performance;
⚫ High temperature tolerance, thermal runaway performance and puncture tolerance;
Foil coated with carbon Seperator
⚫ Optimized VC/FEC to improve the stability of anode; ⚫ Adjusted LiDFOB/LiPFO2 to improve the safety at high and low temperature. ⚫ Optimize the ratio of solvent and lithium salt to improve the stability and safety of electrolyte.
Area density
Eletrolyte
Dura ble
⚫ Improve the NP radio to eliminate the
NP ratio
cathode lithium precipitation, and to
High qualtiy pressing
⚫ Reduce the pressing density of electrodes
Safe
Stable ◆ Technology design
lower IR, reduce the temperature rise, and improve safety
chain
temperature rise, and the side effects ; ⚫ Long life graphite without dendrites to maintain safety
◆ Material
⚫ Reduce the electrode coating area density to
Jelly-roll
improve safety and extend the cycle life.
to inhibit the battery inflation, and to improve the long-term stability and safety.
⚫ Optimize jelly-roll, Avoid battery bulges or excessive resistance,ensure the stability and consistency of the battery cell
Cell plate buffer
⚫ Increase the buffer of the cathode and the separator, to reduce misalignment short circuit, and the safety performance
Safety Design-Pack & System ⚫ The use of insulation materials avoids large areas of heat transfer, to effectively reduce the risk of heat spread. ⚫ Use a resettable pressure relief valve to reduce the risk of overpressure & explosion of the battery pack and prevent excessive air.
⚫ The sampling line is wrapped in a heat-resistant material to reduce the risk of secondary short circuits. ⚫ Three level fire suppression system(FSS) design : ○ Battery Pack - Aerosol ○ Container –NOVEC1230/FM200 ○ Backup water sprinkler fire system
Exploded View ⑬ Horn & Strobe alarm device Industrial Chiller Battery Pack HV Box/ BPU MSD
Deflagration Plate Lifting Ring Gas fire Extinguisher (Optional)
Communication Port Pressure Relief Valve Dehumidifier
Hot water outlet
Cooling water inlet
FSS-Layout Aerosol Pack(Default) or Gas (Optional, FM 200 / Novec 1230) and water pipe fire suppression system (Optional)
• •
Aerosol fire suppression device for each battery pack
• •
Smoke/Gas detector: Photoelectric smoke detector; Heat detector:Fire detection devices that use a network of thermistors to monitor temperature; Horn & Strobe alarm device; 300g aerosol fire extinguishing device
FSS-Main Components No.
Main components
1
Smoke/Gas detector:Photoelectric smoke detector
2
Heat detector:Fire detection devices that use a network of thermistors to monitor temperature
3
Horn & Strobe alarm device
4
Pressure-Releasing system: valve plate
5
300g aerosol fire extinguishing device
6
Aerosol fire extinguishing device bulid in battery pack
FSS Control Strategy
Liquid cooling system-layout
• Temperature difference is well controlled within 3℃ among cells; • The temperature rise of charge and
discharge shall not exceed 4℃; • Refrigeration capacity:8kW Cooling power:4.5kW • Heating capacity:2.5kW Heating power:3.5kW
Piping for cooling system
Industrial Chiller
Liquid chiller Working diagram
Refrigerant Loop
Water Loop
Liquid Cooling System-Function The Chiller consists mainly of a compressor, condenser, throttling component, evaporator, water pump, PTC liquid heater and the necessary control components. The Chiller is used to regulate the temperature of the battery pack in the energy storage system to ensure that it always works within the right temperature range in order to maintain the best working conditions of the system, with the following functions: ⚫ Precise measurement and monitoring of the coolant temperature. ⚫ Effective heat dissipation when the battery pack temperature is high to prevent thermal runaway accidents. ⚫ Pre-heating is working when the battery temperature is low, to raise the battery temperature and ensure charging and discharging performance and safety at low temperatures.
Control strategy of liquid cooling system No.
1
Working mode
Judgment logic
Discharge condition:
After receiving the cooling request sent by BMS,
Cooling is activated when NTC monitoring cell
NTC monitoring cell Tmax≤30℃ & Tvag≤28℃ ,
TMS will start the pump within 20 seconds, and start
Tmax≥32℃&Tvag≥30℃.
Cooling will stop.
the compressor to enter the cooling mode after 30
Cooling mode
seconds. The set target temperature of the Cooling is activated when NTC monitoring cell Tmax≥32℃&Tvag≥30℃. Discharge condition:
When NTC monitors cell unit Tmin≤-10℃|| Tvag≤-5℃, turn on the heating and allow
3 4
5
Heating mode
Standby mode Work mode judgment
and description Fault tolerant processing of TMS control strategy
remark
Discharge condition:
Charging condition:
2
Cut-off condition
small current discharge
Charging condition: NTC monitoring cell Tmax≤30℃ & Tvag≤28℃ .
compressor to start is T=20±1℃@ the environment is 25℃±2℃, and the compressor power will be adjusted according to the water temperature.
Discharge condition: NTC monitoring cell monomer Tmin≥20℃&Tvag≥25℃, turn off the heating.
Charging condition:
Charging condition:
When NTC monitors cell monomer Tmin≤5℃||
NTC monitors the cell mono Tmin≥20℃ &
Tvag≤10℃, turn on heating and prohibit
Tvag≥25℃, turns off the heating and allows
charging;
charging.
PTC heating is regulated by TMS. In heating mode, TMS monitors the cooling liquid heating target temperature T=30℃.
Do not start cooling and heating. The cooling and heating modes have the highest priority and are executed first when they conflict with other modes. When there is a conflict between
the cooling and heating modes, the self-circulation mode is executed. 1. When the communication between BMS and TMS is interrupted, delay 5M, TMS sends alarm code, and automatically enters standby mode, BMS sends
level 1 alarm (without cutting off the main loop relay, the power will be properly reduced, and maintenance processing is requested); 2. When the Chiller fails in the heating and cooling mode, exit and automatically enter the self-cycle mode.
Liquid Cooling System -Thermal Simulation
Ambient temperature 25℃
The highest temperature( ℃)
Temperature rise(℃)
Temperature difference( ℃)
(Ai r co o l i n g ) 2 P1 2S -1 50Ah -0 .5 CP
3 7 .3
1 2 .3
3
( Ai r co o l i n g )1 P2 4S -1 50Ah -1 CP
3 9 .8
1 4 .8
7 .1
(Ai r co o l i n g ) 1 P1 6S -2 80Ah -0 .5 CP
3 3 .9
8 .9
3 .3
( L i qu i d c o o l i n g ) 1 P 52 S - 28 0Ah -0 .5 CP
31.7
6.7
2.9
BMS-Topology Battery Management System (BMS) • Sub-system- BAU monitoring & control BCU and other equipment, charge and discharge management • Sub-system- BCU monitoring & control BMU, & monitoring current & voltage of battery rack • Sub-system- BMU monitoring cell operating data (voltage/temperature)
BMS Internal communication protocol: CAN BMS to EMS/PCS communication protocol:Modbus,IEC61850,IEC104
BMS-Function Component
SBMU
Function
Monitoring the voltage and temperature of single cells in the battery module. Providing data for the battery system control of equalization management. Management of SBMUs for battery voltage and temperature and detection of the discharge current and charging current of the batteries in the same rack. Triggering the protection when current, OCV, Temp etc. exceeds the threshold values by cutting off the relays and
SBCU
reporting to SBAU through CAN bus. Control of the main relay, sampling and processing of current sensor signals, sampling of auxiliary contact feedback signals of the main relay, and leakage detection.
Calculation of the SOC and SOH of the battery rack. Connect with the SBCUs and communicate with the PCS and the monitoring screen, including obtaining voltage, temperature, current, insulation, and relay status reported by SBCUs through internal CAN bus, displaying the
SBAU
BESS status in real-time on the monitoring screen after being connected to it with debugging CAN bus, and communicating with PCS for control of charge and discharge through the external CAN bus. One SBAU (Master *1) will manages the battery information provided by multi SBCUs (slaves*N).
BMS-The advantages of the design scheme Safety --Improvement of the system failure detection, to reduce the possibility of BMS's own malfunction, and reach ASILB level; --Failure diagnosis of broken wires, over-temperature and so on is carried out for the BPU, battery pack and wiring harness, with timely warning and treatment. Reliability -- The DC bus is equipped with "controllable DC circuit breaker", for safe disconnection of the system in case of failure; -- Monitoring of the temperature of B-/B+ of the battery pack, and shutdown of the system in event of the abnormal change of temperature in time; --Software follows the Autosar architecture, greatly reducing the development & optimization cycle.
Intelligence --Intelligent address assignment, which improves the efficiency of on-site commissioning and after-sales; --Intelligent high-voltage management, minimizing the input of after-sales personnel while ensuring safety --Intelligent equalization at battery packs, racks and system to ensure the consistency and maximize the efficiency of the battery system; --Combined with EMS, PCS and backend system to enable battery remote diagnosis, remote control, remote operation and maintenance. Maintenance --Complete system diagnostic information and operation and maintenance tips for easy operation and maintenance.
Battery Pack- Specification No.
Items
Specification parameter
1
Cell specification
280Ah
2
System group mode
1P52S
3
Rated capacity
280Ah
4
Application voltage level
1500V
5
Rated energy
46.592kWh
6
IP protection level
IP67
7
Dimension
D1138*W786*H250mm
8
Weight
Apprx 360kg
9
Application
Standard Battery Pack, outdoor cabinet
4.1 电池包爆炸图
Explosive view of Great Power Battery Pack-Structure Battery Pack cover
Aluminum BUS
Access window
Module insulation sheet
Extinguishing agent inside the pack (aerosol)
Battery sub module 1P12S
Terminal plate 280Ah cell Steel tape
Hight voltage connector(socket) MSD
Relief Valve
Liquid cooling panel BMU(sub control board)
Resin
HV Box Fuse
⚫ BCU ⚫ Isolating switch
Shunt Air switch Isolating switch
⚫ Lightning protector ⚫ UPS & Battery(lead-acid) ⚫ HV relay ⚫ ……
Lightning surge protection
Precharge resistor Manual Disconnector Power switch Precharge relay
HV relay Battery
FAT Factory acceptance tests are designed to test the functionality and integrity of the entire system to ensure that all components and modules are working correctly to achieve the performance of the system. FAT mainly includes the following test items: ⚫ Dimensional check ⚫ Torque and tension test ⚫ Ground resistance test ⚫ Withstand voltage/ Hi-POT test ⚫ Charge, discharge and capacity test ⚫ Communication function test ⚫ HVAC/TMS function test ⚫ FSS function test ⚫ Waterproofing test ⚫ ........
Process flow chart
Procedure 1: Pack assembly (see paper CP file for details)
Process flow chart Enclosure Unloading
Enclosure SN identification
Power Cable connection
Communication Cable connection
Cabinet Test
Power & Communication cables Installation
BMS Aux Cable Installation
BPU Installation
Battery Pack Installation
Cabinet Shipment
Step 2: Battery rack installation and system testing (see paper CP file for details)
Certifications ESS global certificate list North America
Items
Europe
IEC62619 IEC62477 EMC (FS IEC & (IEC61000 IEC62933 AS3000 AS5139 60730-1) IEC62040 )
transpor t
GB/T 36276
UL9540A (2019)
UL9540 (2023)
PASS
PASS
/
PASS
/
PASS
/
/
/
/
/
PASS
24/03
PASS
/
/
/
/
/
/
/
/
/
PASS
Rack
PASS
/
/
/
/
PASS
/
PASS
/
/
/
/
Cabinet
/
PASS
PASS
PASS
comply
PASS
PASS
PASS
comply
Standard
Cell Battery Module
UL1973 NFPA855 (2022) (NFPA68)
Australia
comply comply
UN38.3
PASS
Compatible PCS PCS C Rate
Name of manufacturer
Dc side
Ac side
Model number
Battery voltage range
Cabinet No. at Max C rate
Rated AC power
FC1440ML
1120 - 1500 V
8
1440KW
FC2160ML
1120 - 1500 V
12
2160KW
FC2880ML 0.5C/0.33C/ INDRIVITEC 0.25C
1120 - 1500 V
16
2880KW
FC3600ML
1120 - 1500 V
20
3600KW
FC4320ML
1120 - 1500 V
20 (Short-circuit current TBC)
4320KW
Rated AC voltage
690V
Applicability Rated frequency
50/60Hz
Safety certification
Grid-connected certification
Applicable country
EN61000-6-2, EN61000-6-4, EN62477-1, IEC62103
Eu EN 50530, EN 505492, Italy CEI 0-16, Germany VDE-AR-N 4120, VDE-AR-N 4110, UK G99,
Most of Europe
Compatible PCS
PCS C Rate 0.5C/ 0.33C /0.25 C
Dc side
Ac side
Applicability
Name of manufacturer
Model number
Battery voltage range
Battery Cluster No. at Max C rate
Rated AC power
Rated AC voltage
Rated frequency
Safety certification
Grid-connected certification
Applicable country
KACO
Gridsave 92.0 TL3-S
668 - 1315 V
1
92KW
400V
50/60Hz
IEC 62477-1:2012, IEC 621091/2
/
EU
DYNAPOWE R
DYNAPO WER MPS125
730V-1500V
1
125KW
480V
60Hz
UL1741 SA\NFPA70\IEEE519 IEEE 1547.1:2020
USA